What are the general requirements for the layout of the compressor?

(1) The arrangement of the compressor unit and its ancillary equipment shall meet the requirements of the manufacturer; (2) the compressor shall be arranged near the equipment to be pumped, and its ancillary equipment shall be arranged close to the unit; (3) Arrangement of the combustible gas compressor The following requirements shall be met: 1) The distance from open flame equipment and non-explosion-proof electrical equipment shall comply with the current national standards “Code for Design of Explosive and Fire Hazardous Environment Power Equipment” GB50028 and “Design Rules for Fire Protection of Petrochemical Enterprises” GB50160; ) should be arranged in the open air or semi-open. It can be arranged in the factory in cold or windy sand areas; 3) Class A gas compressor plant with single drive power equal to or greater than 150kw, it is not suitable to share a building with other Class A, B and C rooms; above the compressor, Class A, B, and C liquid equipment shall not be arranged, but the high-grade lubricating oil tank for own use is not subject to this limitation.
(4) For single-layer compressors, when the foundation is high, the operating platform should be set as required; when there are more auxiliary equipments, it is better to arrange them in two layers.